BIGTheme.net • Free Website Templates - Downlaod Full Themes

Hot Connections

hot-connections-infrared

Atmospheric Temperature 20.0 °C
Object Distance 2.0 m
Image Zoom Factor 1.0
Ar1 Max. Temperature >60.3 °C
Ar1 Min. Temperature 25.6 °C
Ar1 Max - Min Temperature 34.8 °C
Ar1 Emissivity 0.92

 

Line Name: Viana – Camama

Conductor type: ACSR Cow Single Conductor

Priority: 1

Tower Info:

  • Tower Number 31 from Camama
  • B Side Bottom Phase
  • Incorrect torque applied to bolts

Cause: Can Lead To Structural Damage And Total Loss Of Supply.

.